Knowledge Base

Current Converter

Current Convert Chart of Difference Voltage for Design of Motor (Three Phase)

HP   Voltage Range
  200 230 260 290 320 350 380 410 440 460
0.50 Current AMP. 2.5 2.2 1.9 1.7 1.6 1.4 1.3 1.2 1.2 1.1
0.75 3.7 3.2 2.8 2.5 2.3 2.1 1.9 1.8 1.7 1.6
1.00 4.8 4.2 3.7 3.3 3.0 2.8 2.5 2.4 2.2 2.1
1.50 6.9 6.0 5.3 4.8 4.3 3.9 3.6 3.4 3.1 3.0
2.00 7.8 6.8 6.0 5.4 4.9 4.5 4.1 3.8 3.6 3.4
3.00 11.0 9.6 8.5 7.6 6.9 6.3 5.8 5.4 5.1 4.8
4.00 14.7 12.8 11.3 10.2 9.2 8.4 7.7 7.2 6.7 6.4
5.00 17.5 15.2 13.4 12.1 10.9 10.0 9.2 8.5 7.9 7.6
6.00 22.1 19.2 1.0 15.2 13.8 12.6 11.6 10.8 10.0 9.6
7.50 25.3 22.0 19.5 17.4 15.8 14.5 13.3 12.3 11.5 11.0
10.00 32.2 28.0 24.8 22.2 20.1 18.4 16.9 15.7 14.6 14.0
12.50 40.9 35.6 31.5 28.2 25.6 23.4 21.5 20.0 18.6 17.8
15.00 45.3 42.0 37.2 33.3 30.2 27.6 25.4 23.6 22.0 21.0
17.50 56.6 49.2 43.5 39.0 35.4 32.3 29.8 27.6 25.7 24.6
20.00 62.1 54.0 47.8 42.8 38.8 35.5 32.7 30.0 28.2 27.0
22.50 71.3 62.0 54.8 49.2 44.6 40.7 37.5 34.8 32.4 31.0
25.00 78.2 68.0 60.2 53.9 48.9 44.7 41.2 38.1 35.5 34.0
27.50 86.9 75.6 66.9 60.0 54.3 49.7 45.8 42.4 39.5 37.8
30.00 92.0 80.0 70.8 63.4 57.5 52.6 48.4 44.9 41.8 40.0
32.00 99.6 86.6 76.6 68.7 62.2 56.9 52.4 48.6 45.3 43.3
35.00 104.7 91.0 80.5 72.2 65.4 59.8 55.1 51.0 47.6 45.5
40.00 119.6 104.0 92.0 82.5 74.8 68.3 62.9 58.3 54.4 52.0
45.00 134.6 117.0 103.5 92.8 84.1 76.9 70.8 65.6 61.2 58.5
50.00 149.5 130.0 115.0 103.1 93.4 85.4 78.7 72.9 68.0 65.0

Current Convert Chart of Difference Voltage for Design of Motor (Single Phase)

HP Current AMP. Voltage Range
100 120 140 160 180 200 220 240
0.50 11.2 9.3 8.0 7.0 6.2 5.6 5.1 4.7
0.75 15.8 13.2 11.3 10.3 8.8 7.9 7.2 6.6
1.00 18.4 15.3 13.1 11.5 10.2 9.2 8.4 7.7
1.50 23.0 19.2 16.4 14.4 12.8 11.5 10.5 9.6
2.00 27.6 23.0 19.7 17.3 15.3 13.8 12.5 11.5
3.00 39.2 32.7 28.0 24.5 21.8 19.6 17.8 16.3
4.00 55.2 46.0 39.4 34.5 30.7 27.6 25.1 23.0
5.00 64.4 53.7 46.0 40.3 35.8 32.2 29.3 26.8

Cable Selection Information

Cable Selection Chart at 415 V (Single Cable with DOL Stater) Three Phase

HP AMP Cable Size(Sq. mm) Length in Meters
10 20 20 30 40 50 60 70 80 90 100 120 140 160 180 200 250 300 350 400 450 500
0.5 1.5 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.5 1.5 1.5
1.0 2.5 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.5 1.5 1.5 1.5 1.5 1.5
1.5 3.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5
2.0 3.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5
3.0 5.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 2.5 2.5 2.5 2.5
4.0 7.0 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5
5.0 7.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 2.5 2.5 2.5 4 4 4 4 4 4 4 4
6.5 10.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 2.5 2.5 2.5 4 4 4 4 4 4 4 4 6
7.5 11.0 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 2.5 2.5 4 4 4 4 4 4 4 4 6 6
10 15.0 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 4 4 4 4 6 6 6 6 6 6 10 10
12.5 19.0 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 4 4 4 6 6 6 10 10 10 10 10 16 16
15 23.0 4 4 4 4 4 4 4 4 4 4 4 6 6 6 10 10 10 10 10 10 16 16
17.5 26.0 4 4 4 4 4 4 4 4 4 4 6 6 6 10 10 10 10 10 10 10 16 16
20 29.0 6 6 6 6 6 6 6 6 6 6 6 6 10 10 10 10 10 10 10 16 16 16
22.5 32.0 6 6 6 6 6 6 6 6 6 6 6 10 10 10 10 10 10 10 10 16 16 16
25 36.0 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 16 16 16 16 16 25 25
30 43.0 10 10 10 10 10 10 10 10 10 10 10 10 10 10 16 16 16 16 16 16 25 25
35 51.0 10 10 10 10 10 10 10 10 10 10 10 10 10 16 16 16 16 16 16 25 25 25
40 59.0 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 25 25 25 25
45 63.0 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 25 25 25 25 25
50 68.0 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 25 25 25 25 25 25

Cable Selection Chart For 230V, 50 Hz, Single Phase

HP   Length in Meters
10 20 30 40 50 60 70 80 90 100 120 140 160 180 200 250 300 350 400 450 500
0.5 Cable Size(Sq. mm) 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 2.5 2.5 2.5 4.0 4.0 4.0 6.0 6.0 6.0 10.0 10.0
1.0 1.5 1.5 1.5 1.5 1.5 1.5 2.5 2.5 2.5 2.5 4.0 4.0 4.0 6.0 6.0 6.0 10.0 10.0 10.0 16.0 16.0
1.5 1.5 1.5 1.5 1.5 2.5 2.5 4.0 4.0 4.0 6.0 6.0 10.0 10.0 10.0 10.0 16.0 16.0 16.0 25.0 25.0 25.0
2.0 2.5 2.5 2.5 2.5 4.0 4.0 4.0 6.0 6.0 6.0 10.0 10.0 10.0 16.0 16.0 16.0 25.0 25.0 25.0 35.0 35.0
3.0 2.5 2.5 2.5 2.5 4.0 4.0 6.0 6.0 6.0 10.0 10.0 10.0 16.0 16.0 16.0 16.0 25.0 25.0 25.0 35.0 35.0
4.0 2.5 2.5 2.5 4.0 4.0 6.0 6.0 10.0 10.0 10.0 10.0 16.0 16.0 16.0 16.0 25.0 25.0 25.0 35.0 35.0 35.0
5.0 2.5 2.5 4.0 4.0 6.0 6.0 10.0 10.0 10.0 10.0 16.0 16.0 16.0 25.0 25.0 25.0 35.0 35.0 50.0 50.0 50.0

Cable Selection Chart at 415 V (Double Cable with Star Delta Stater), Three Phase

HP AMP   Length in Meters
  10 20 30 40 50 60 70 80 90 100 120 140 160 180 190 200 250 300 350 400 450 500
5.0 7.5 Cable Size(Sq. mm) 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 2.5 2.5 2.5 2.5
6.5 10.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 2.5 2.5
7.5 11.0 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 4 4
10.0 15.0 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 2.5 2.5 2.5 2.5 2.5 2.5 4 4 4 4 4
12.5 19.0 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 2.5 2.5 4 4 4 4 6 6 6 6 6
15.0 23.0 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 4 4 4 4 4 4 4 4 4 4
17.5 26.0 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 4 4 4 4 4 4 4 4 4 6 6
20.0 29.0 4 4 4 4 4 4 4 4 4 4 4 4 4 6 6 6 6 6 6 6 8 8
22.5 32.0 4 4 4 4 4 4 4 4 4 4 4 4 6 6 6 6 6 6 6 8 8 8
25.0 36.0 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 8 8 8 8 8 8
30.0 43.0 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 8 8 8 8 8 8 8
35.0 51.0 6 6 6 6 6 6 6 6 6 6 6 6 8 8 8 8 8 8 8 8 10 10
40.0 59.0 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 10 10 10 10
45.0 63.0 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 10 10 10 10 10 10
50.0 68.0 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 10 10 10 10 10 10 10

Open Pipe Flow Measurement Method

Discharge Rate Table

Horizontal Distance "X" in Inches Nominal Pipe Diamter "D"
1" 1.25" 1.5" 2" 2.5" 3" 4" 5" 6"
Discharge Rate (Q) (Liters Per Minute)
4 24 40 58 98 135 210 370 595 855
5 33 60 78 130 175 285 475 745 1125
6 40 70 94 154 210 335 575 890 1275
7 43 80 110 183 245 385 669 1055 1545
8 49 95 124 204 185 450 750 1185 1758
9 60 105 140 232 320 508 843 1355 1968
10 68 112 156 254 345 564 965 1465 2135
11 72 119 171 283 385 610 1025 1645 2375
12 76 135 180 308 430 674 1110 1765 2605
13 82 146 200 333 458 725 1234 1940 2795
14 90 157 218 349 489 780 1315 2048 3036
15 98 168 234 380 535 848 1420 2245 3218
16 103 177 244 398 570 895 1505 2375 3425
17 110 190 262 425 610 940 1615 2505 3648
18 114 205 278 450 540 1002 1695 2688 3868
19 120 215 286 480 675 1055 1805 2824 4124
20 130 225 305 510 710 1114 1885 2958 4339
21 138 238 321 530 750 1160 1990 3105 4526
22 145 245 338 560 785 1225 2105 3248 4752
23 150 258 349 583 820 1281 2195 3425 4988
24 155 269 368 602 859 1325 2278 3554 5148
25 162 277 376 635 894 1395 2368 3716 5397
26 170 290 398 655 932 1449 2474 3848 5614
27 178 305 408 680 968 1508 2554 4015 5820
28 185 315 428 708 1005 1549 2654
29 190 324 442 725 1035 1615 2749
30 195 336 456 767 1068 1670 2845
31 470 784 1102 1725
32 484 810 1142 1785
33 502 830 1175 1836
34 515 862 1225 1891
35 531 888 1274 1975
Knowledge Base | Siphon Pumps, Rajkot, Gujarat, India

Standard Instruction & Preventive Measures

  • Use ISI marked and low friction good quality pipes, cable & motor starter.
  • Pump should be run for few minute at least once in 2 days to prevent it from seizing.
  • Pump should not be operated dry. Install dry run preventer to protect the pump set from running dry.
  • Earthing is compulsory.
  • Distance of cable (motor to starter), elbows, tee and bands directly affect the performance of pump.
  • Best efficiency of pump at duty point (S1 Duty).
  • The performance data are at rated voltage (50 Hz) and are only indicative.
  • Pipe sizes mentioned in mm are nominal pipe sizes and are nearest conversion on inches, pipe threads are provided as per BSP standard.
  • Any type of change is not valid in our product because the design of our model is directly connected to winding data.

Special Features And Material of & Construction

  • Excellent quality SS-202 grade pump pipe and motor body.
  • Noryl lass filled bowl set.
  • Power of endurance in pressure bowl design.
  • CRNOM-47 (cold non-grain orientale) stamping of motor.
  • Copper: EC grade.
  • Shaft: SS410 grade.
  • Available in single and three phase.
  • Used in agriculture, industries, domestic and gardening.
  • Head range 18m to 385m
  • Balanced impellers.
  • High Quality Mechanical seal.
  • High quality packaging to prevent damage during transit.
Volt after pump gets started Three Phase Single Phase
Three Phase Volt (V) Single Phase Volt (V) Reduction Head (%) Reduction of Dis. (%) Reduction Head (%) Reduction of Dis. (%)
415 240 NIL NIL NIL NIL
350 200 5 5 5 3
310 180 10 8 8 6
275 160 15 12 12 9
240 140 20 15 16 12
Frequency (Hz) Change in output Change in total
output (%)
Head (%) Dis. (%)
51 +4 +2 +6
Std. 50 Std. Std. NIL
49.5 -2 -1 -3
49.0 -4 -2 -6
48.5 -6 -3 -9
48.0 -8 -4 -12
47.5 -10 -5 -15

V3, V4, V6 & Openwell Single Phase Pump Set Capacitor Selection Chart

Three Phase Volt (V) VOLT
  120 160 220
0.50 Cable Size(Sq. mm) 50+36 50 36
0.75 36+36+36+ 50+25 50
1.00 50+36+36 36+50 36+25
1.50 50+50+36 36+36+36 36+36
2.00 50+50+36 36+36+36 36+36
3.00 50+50+50+36 50+50+36 36+36+36
5.00 50+50+50+50 50+50+50 36+36+50